LoadZ

Static constant-impedance load model. LoadZ owns terminal current states and adds their current contribution to the connected bus residual.

Model Parameters

Symbol

Units

JSON

Description

Typical Value

Note

\(R\)

[p.u.]

R

Load resistance

\(X\)

[p.u.]

X

Load reactance

Parameter Validation

None.

Model Derived Parameters

\[\begin{split}\begin{aligned} G &= \dfrac{R}{R^2 + X^2} \\ B &= -\dfrac{X}{R^2 + X^2} \end{aligned}\end{split}\]

Model Ports

Name

Port

Init

Description

bus

Bus

Known

Connected bus that owns terminal voltage variables and current-balance residuals

Model Variables

Internal Variables

Differential

None.

Algebraic

Symbol

Units

Description

Note

\(I_r\)

[p.u.]

Terminal current, real component

Added to connected bus residual

\(I_i\)

[p.u.]

Terminal current, imaginary component

Added to connected bus residual

External Variables

Differential

None.

Algebraic

Symbol

Units

Description

Note

\(V_r\)

[p.u.]

Terminal voltage, real component

Owned by connected bus

\(V_i\)

[p.u.]

Terminal voltage, imaginary component

Owned by connected bus

Model Equations

Internal Equations

Differential

None.

Algebraic

\[\begin{split}\begin{aligned} 0 &= I_r + G V_r - B V_i \\ 0 &= I_i + B V_r + G V_i \end{aligned}\end{split}\]

External Equations

\[\begin{split}\begin{aligned} I_r^{\mathrm{bus}} &\leftarrow I_r^{\mathrm{bus}} + I_r \\ I_i^{\mathrm{bus}} &\leftarrow I_i^{\mathrm{bus}} + I_i \end{aligned}\end{split}\]

Initialization

The initial bus voltage determines the terminal currents:

\[\begin{split}\begin{aligned} I_r &\leftarrow -G V_r + B V_i \\ I_i &\leftarrow -B V_r - G V_i \end{aligned}\end{split}\]

The derivative vector entries initialize to zero.

Monitors

Monitor

Units

Description

Note

p

[p.u.]

Active power at the connected bus terminal

Positive for injection into the connected bus

q

[p.u.]

Reactive power at the connected bus terminal

Positive for injection into the connected bus